Basic data
Model |
Nominal volume flow (VN)*1 |
Capacity*2 | Max. operating pressure | Min./Max. operating temperature |
FCA90CMSM |
0,5 m³/h |
11 m³ |
16 bar | +2°C – +45°C |
FCA110CMSM |
1.5 m³/h |
32 m³ |
||
FCA120CMSM |
2.5 m³/h |
54 m³ |
||
FCA130CMSM |
4.0 m³/h |
95 m³ |
*1 – refers to 1 bar(a) and 20°C at 7 bar operating pressure for 10 seconds contact time of the compressed air inside the desiccant bed
Reducing the volume flow improves all specifications
*2 – refers to 20°C inlet temperature (17.15 g/m³ humidity) and 20% load capacity of the desiccant referred to its weight
Purity classes according to ISO 8573-1
Contamination |
|
Solid particles |
(Class 2) |
Water content *3 |
Class 2 |
Total oil content |
— |
*3 – typical result, on the assumption of suitable inlet concentrations as well as operating and marginal conditions.
Volume flow conversion factors
«F1» – Pressure (in bar)
0 |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
15 |
16 |
0.125 |
0.25 |
0.38 |
0.50 |
0.63 |
0.75 |
0.88 |
1.00 |
1.13 |
1.25 |
1.38 |
1.50 |
1.63 |
1.75 |
1.88 |
2.00 |
2.13 |
«F2» – Temperature (in °C)
2 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
1.07 |
1.05 |
1.04 |
1.02 |
1.00 |
0.98 |
0.97 |
0.95 |
0.94 |
0.92 |
Calculation of the converted volume flow
Converted volume flow VK |
Nominal required volume flow VNmin |
VK = VN x F1 x F2 |
VNmin = VK / F1 / F2 |
VK : Converted volume flow calculated for the operating conditions
VNmin: Nominal required volume flow calculated for the operating conditions, based on the volume flow at operating conditions
Maintenance rules
Pressure range |
|
Entire pressure range |
Replacement of filter cartridge depending on the operating temperature and there-fore on the specified vapour amount (use of a humidity indicator or dewpoint meter is recommended) In the course of filter cartridge replacement or cleaning: checking for serious corrosion |
Product specific data
Specification |
|
Differential pressure |
< 50 mbar |
Pressure dew point (nominal) |
-40°C |
Materials
Component |
|
Filter housing |
Aluminium (16 bar VDS no.: 233 ; 50 bar VDS no.: 239 heat treated) |
Coatings |
Inside and outside: Chrome(VI)-free thin-film passivation ; min. layer thickness 5μ Outside: 1-component power coating epoxide/polyester basis, layer thickness appr. 80 μ |
Mounting parts, fittings |
Brass, brass (nickel-plated), steel (galvanically zinc-plated) |
Sealing materials |
NBR, Teflon (FCA140-190) |
Lubricants |
Rivolta S.K.D. 4002 or similar |
Filling |
Molecular sieve (MS) |
Filter cloths |
Polyester-Polyurethane |
Mesh screens |
Stainless steel 1.4301 |
Filter media general purpose filtration |
Glass fibre |
Bonded joint |
PU (Polyurethane) |
Cylinder filling |
Acrylic |
Cylinders filter media |
Stainless steel 1.4301 |
End caps |
PA6 (Polyamide) |
Sealing materials |
NBR |
Connections, dimensions and weight
Model |
Connection |
Condensate Outlet |
Height |
Width |
Depth |
Weight |
FCA90CMSM |
G 1/2 |
CDM14N |
311 mm |
130 mm |
122 mm |
4.0 kg |
FCA110CMSM |
G 1/2 |
CDM14N |
409 mm |
130 mm |
122 mm |
4.4 kg |
FCA120CMSM |
G 1/2 |
CDM14N |
509 mm |
130 mm |
122 mm |
4.8 kg |
FCA130CMSM |
G 1/2 |
CDM14N |
711 mm |
130 mm |
122 mm |
5.8 kg |
Classification according to Pressure Equipment Directive 2014/68/EU for group 2 fluids
Model |
Volume |
Category |
Commissioning inspection*6 |
Routine inspection*6 |
FCA90CMSM |
1.46 litres |
— |
— |
— |
FCA110CMSM |
2.19 litres |
— |
— |
— |
FCA120CMSM |
2.91 litres |
— |
— |
— |
FCA130CMSM |
4.36 litres |
I |
AP*7 |
— |